In this lesson we will be doing a CPC test on a simple lighting circuit.
You can pause and rewind the how-to video and jump in and out of the Electrical Virtual Reality at any point.
Bridge the line conductor to the protective conductor at the distribution board so as to
include all the circuit. Then test between line and earth terminals at each point in the
circuit. The measurement at the circuit's extremity should be recorded and is the value
of (R1 + R2) for the circuit under test (see Figure 10.3.1(i)).
If the instrument does not include an 'auto-null' facility, or this is not used, the resistance
of the test leads should be measured and deducted from the resistance readings obtained.
After you finish we would love you to fill out some feedback so we can improve the system further.